Call-out · Y-Plan

Hot water only when the heating is on too (Y-Plan)

“We only get hot water when the heating is on as well.”

In short

Hot water only heats while the heating is also on. Confirm it for yourself, then follow the demand with the meter: the fault lies between the last point with 230 V and the first without.

What the customer says

  • “We only get hot water when the heating is on as well.”

The customer’s words are where you start, not what you trust. Confirm the complaint for yourself before you pick up the meter: set one demand at a time and watch what each part does.

What it already proves

On a Y-Plan the valve RESTS at hot water, so for hot water alone the valve does nothing. Ask what should fire the boiler for hot water ONLY.

The method

If this is your home: this page is written for heating engineers. Mains wiring and gas appliances are not DIY jobs; call a Gas Safe registered engineer. If you smell gas, leave the building and call the National Gas Emergency Service on 0800 111 999.

In the simulator the meter is safe. On site: isolate and prove dead before you touch a terminal, and make live tests only if you are trained and equipped for them. The steps below are the method as practised in the simulator, in its own words, for competent persons and for learners under the supervision of one.

  1. 01

    CONFIRM the complaint yourself: spur ON, run the simulation. Ask for one thing at a time: the heating, then the hot water if it has its own control. Watch what each part does.

  2. 02

    On a Y-Plan the valve RESTS at hot water, so for hot water alone the valve does nothing.

  3. 03

    What should fire the boiler for hot water only? The cylinder stat's CALL contact.

  4. 04

    Meter the cylinder stat call terminal, then the boiler's SL.

  5. 05

    The fault lies between the LAST point with 230 V and the FIRST without.

  6. 06

    ISOLATE before you touch anything: the fused spur OFF, locked off, proved dead with a proved tester. Then stop the simulation: the simulator only erases when stopped. Continuity only on a dead circuit.

  7. 07

    Click Report Fault, then the wire or part you have PROVEN faulty.

Where to probe

  • The black probe stays on a neutral for the whole trace. The red probe follows the live from point to point, in the order the demand travels.
  • Between two points, one with 230 V and the next without, there is only a wire, a screw or a part.
  • Prove a part with two readings before you condemn it. A motor needs a live and a neutral: measure across it, to its own neutral.
  • Continuity and resistance only on a circuit that is isolated and proved dead.

Follow the path on the diagram

Metering a Y-Plan in the DrawWarm simulator

The parts on the path, and where to practise

Practise it

  • Random Fault

    One hidden fault at a time, Easy, Medium or Hard

Other call-outs

  • No heating

    “Hot water's fine but the radiators are stone cold, whatever I do with the thermostat.”

  • No hot water

    “Heating's lovely and warm but there's no hot water - the cylinder's cold.”

  • Everything dead

    “Nothing works. No heating, no hot water, and the controls are dead.”

  • Boiler not firing

    “The programmer's on and I can hear things whirring, but the boiler never fires - no heating and no hot water.”